13
|
Troubleshooting
Installer reference guide
176
C08AF + EHYKOMB33A
Daikin Altherma R Hybrid
4P471761-1E – 2020.10
13.3.2 Symptom: The compressor does NOT start (space heating)
Possible causes
Corrective action
The unit must start up out of its
operation range (the water
temperature is too low)
If the water temperature is too low, the
unit uses the gas boiler to reach the
minimum water temperature first
(15°C).
Check and make sure that:
▪
The power supply to the gas boiler is
correctly wired.
▪
The communication cable between
the gas boiler and the indoor unit is
properly mounted.
If the problem persists after you have
conducted all of the above checks,
contact your dealer.
13.3.3 Symptom: The system is making gurgling noises after commissioning
Possible cause
Corrective action
There is air in the system.
Purge air from the system.
(a)
Various malfunctions.
Check if is displayed on the home
pages of the user interface. You can
press to display more information
about the malfunction.
(a)
We recommend to purge air with the air purge function of the unit (to be performed by
the installer). If you purge air from the heat emitters or collectors, mind the following:
WARNING
Air purging heat emitters or collectors.
Before you purge air from heat emitters or
collectors, check if an error or is displayed on the home pages of the user
interface.
▪
If not, you can purge air immediately.
▪
If yes, make sure that the room where you want to purge air is sufficiently
ventilated.
Reason:
Refrigerant might leak into the water circuit, and
subsequently into the room when you purge air from the heat emitters or
collectors.
13.3.4 Symptom: The pump is making noise (cavitation)
Possible causes
Corrective action
There is air in the system
automatic air purge function (see
perform an automatic air
purge"
158]).