7.12.6 Flue pipe position
See the local and national regulations.
Especially for UK:
Only use flue products approved by the boiler manufacturer, which can be bought
from the supplier of your boiler.
See
"5.3 Combining units and options"
27].
P
S
C
B
A
M
R
D
J
Q
G
A
Q
Q
N
P
T2
T2
T2
T1
H
T
I
K
L
F
F
N
E
Terminal position
Minimum distance
(mm)
A
Directly below an open able window or other
opening (e.g. air brick)
300
B
Below gutters, soil pipes or drain pipes
75
C
Below eaves
200
D
Below balconies or car front roofs
E
From vertical drain pipes and soil pipe
150
F
From internal or external corners
300
G
Above ground, roof or balcony level
H
From a surface facing a terminal
600