Special remark regarding
C
43
:
See the table below for the minimum diameters of
the combined gas exhaust/air intake system.
Number of
units
Concentric
Dual pipe
Gas exhaust
Air intake
Gas exhaust
Air intake
2
161
302
161
255
3
172
322
172
272
4
183
343
183
290
5
195
366
195
309
6
206
386
206
326
7
217
407
217
344
8
229
429
229
363
9
240
449
240
380
10
251
470
251
398
11
263
493
263
416
12
274
513
274
434
13
286
536
286
453
14
297
556
297
470
15
308
577
308
488
16
320
599
320
507
17
331
620
331
524
18
342
641
342
541
19
354
663
354
560
20
365
683
365
578
Special remark regarding
C
93
:
The minimum inner dimensions of the chimney have
to be 200×200 mm.
INFORMATION
In case of a C
13
type flue gas system, a flue gas flap valve (EKFGF1A) is recommended.
7.12.5 Applicable materials
Materials for the installation of the gas exhaust and/or air intake MUST be bought
according to the table below.
D BG BA
HR HU SK
SI
CZ
ES PT PL GR CY IE TR
MT LT
LT LV UK FR
B
Daikin
Daikin
Daikin
Daikin
Daikin
Daikin
(b) (a)
(a)
(a)
(b)
C
C
C
C
93
C
C
C
83
63
53
43
33
13
IT
CH AT
(b)
a
Gas exhaust/air intake parts can be bought from a third party. All parts purchased
from an external supplier MUST comply with EN14471.