7
|
Installation
Installer reference guide
96
C08AF + EHYKOMB33A
Daikin Altherma R Hybrid
4P471761-1E – 2020.10
Terminal position
Minimum distance
(mm)
I
From a terminal discharging towards another
terminal
1200
J
From an opening in a car port (e.g. door,
window) into a dwelling
K
Vertically from a terminal on the same wall
1500
L
Horizontally from a terminal on the same wall
300
M
Above an opening, air brick, opening windows,
etc.
N
Horizontally to an opening, air brick, opening
windows, etc.
P
Above roof level (to base terminal)
Q
From an adjacent wall to flue
R
From an adjacent opening window
1000
S
From another roof terminal
600
-
From an external boundary. Note: If the
terminal is facing a boundary, it is
recommended that an anti-plume kit be fitted.
T
T1
T2
Terminals adjacent to windows or openings on
pitched and flat roofs: The flue should NOT
penetrate this area.
2000
600
NOTICE
The boiler manufacturer cannot be held responsible for atmospheric conditions
when siting flue terminals.
CAUTION
Once the flue system has been installed and the appliance commissioned, the
installer should observe the plume direction. Particular attention should be drawn to
plume vapour reentering the gas boiler via the air intake. If this occurs, it is highly
possible the flue is fitted with a negative pressure area and therefore a plume
management kit MUST be fitted.
7.12.7 Insulation of the gas exhaust and air intake
Condensation may occur on the outside of the pipe material when the material
temperature is low and the environment temperature is high with a high humidity.
Use 10 mm damp-proof insulation material when there is a risk of condensation.
7.12.8 Fitting a horizontal flue system
The 60/100 mm horizontal flue system may be extended up to a maximum length
as specified in the table indicating the maximum pipe lengths. Calculate the
equivalent length according to the specifications in this manual.