8
|
Configuration
Installer reference guide
109
C08AF + EHYKOMB33A
Daikin Altherma R Hybrid
4P471761-1E – 2020.10
#
Code
Description
[A.2.1.8]
[7-02]
The system can supply leaving water to up to 2
water temperature zones. During configuration,
the number of water zones must be set.
Number of LWT zones
:
▪
0 (
1 LWT zone
)(default): Only 1 leaving water
temperature zone. This zone is called the main
leaving water temperature zone.
a
▪
a: Main LWT zone
continued >>
#
Code
Description
[A.2.1.8]
[7-02]
<< continuation
▪
1 (
2
LWT
zones
): 2 leaving water
temperature zones. The zone with the lowest
leaving water temperature (in heating) is called
the main leaving water temperature zone. The
zone with the highest leaving water
temperature (in heating) is called the additional
leaving water temperature zone. In practice,
the main leaving water temperature zone
consists of the higher load heat emitters and a
mixing station is installed to achieve the
desired leaving water temperature.
a
b
c
▪
a: Add LWT zone
▪
b: Main LWT zone
▪
c: Mixing station