8
|
Configuration
Installer reference guide
117
C08AF + EHYKOMB33A
Daikin Altherma R Hybrid
4P471761-1E – 2020.10
#
Code
Description
[7.7.2.1]
[0‑00]
[0‑01]
[0‑02]
[0‑03]
Set weather-dependent heating
:
[0-00]
[0-01]
Ta
Tt
[0-03]
[0-02]
▪
T
t
: Target leaving water temperature
(additional)
▪
T
a
: Outdoor temperature
continued >>
#
Code
Description
[7.7.2.1]
[0‑00]
[0‑01]
[0‑02]
[0‑03]
<< continuation
▪
[0‑03]: Low outdoor ambient temperature. –
40°C~+5°C (default: –10°C).
▪
[0‑02]: High outdoor ambient temperature.
10°C~25°C (default: 15°C).
▪
[0‑01]: Desired leaving water temperature
when the outdoor temperature equals or
drops below the low ambient temperature.
[9‑05]°C~[9‑06]°C (default: 60°C).
Note:
This value should be higher than [0-00]
as for low outdoor temperatures warmer
water is required.
▪
[0‑00]: Desired leaving water temperature
when the outdoor temperature equals or
rises above the high ambient temperature.
[9‑05]°C~min(45, [9‑06])°C (default: 35°C).
Note:
This value should be lower than [0-01]
as for high outdoor temperatures less warm
water is required.
Pump control: Flow target
The hybrid module is designed to operate with a fixed flow. This means that the
pump is controlled to work at a flow target set by the installer. The installer can set
the flow target for:
▪
heat pump only operation,
▪
hybrid operation,
▪
gas boiler only operation.