8
|
Configuration
Installer reference guide
115
C08AF + EHYKOMB33A
Daikin Altherma R Hybrid
4P471761-1E – 2020.10
INFORMATION
▪
The primary energy factor can always be set, but is only used in case the savings
mode is set to
Ecological
.
▪
To set electricity price values, do NOT use overview settings. Set them in the
menu structure instead ([7.4.5.1], [7.4.5.2], and [7.4.5.3]). For more information
on how to set the energy prices, see the operation manual and the user
reference guide.
Space heating control
The basic required settings in order to configure the space heating of your system
are described in this chapter. The weather-dependent installer settings define the
parameters for the weather-dependent operation of the unit. When weather-
dependent operation is active, the water temperature is determined automatically
depending on the outdoor temperature. Low outdoor temperatures will result in
warmer water and vice versa. During weather-dependent operation, the user has
the possibility to shift up or down the target water temperature by a maximum of
10°C.
See the user reference guide and/or operation manual for more details about this
function.
Leaving water temperature: Main zone
#
Code
Description
[A.3.1.1.1]
N/A
LWT setpoint mode
:
▪
Fixed
:
The
desired
leaving
water
temperature is:
-
NOT weather-dependent (i.e. does NOT
depend
on
the
outdoor
ambient
temperature)
-
fixed in time (i.e., NOT scheduled)
▪
Weather dep.
(default): The desired leaving
water temperature is:
-
weather-dependent (i.e. depends on the
outdoor ambient temperature)
-
fixed in time (i.e., NOT scheduled)
#
Code
Description
[7.7.1.1]
[1‑00]
[1‑01]
[1‑02]
[1‑03]
Set weather-dependent heating
:
[1-03]
[1-02]
Ta
Tt
[1-00]
[1-01]
▪
T
t
: Target leaving water temperature (main)
▪
T
a
: Outdoor temperature
continued >>