15
|
Technical data
Installer reference guide
200
C08AF + EHYKOMB33A
Daikin Altherma R Hybrid
4P471761-1E – 2020.10
15.5 Table 2 – Minimum floor area: indoor unit
m
c
(kg)
Minimum floor area (m²)
H=500 mm,
600 mm,
700 mm
H=800 mm
H=900 mm
H=1000 mm
H=1100 mm
H=1200 mm
H=1300 mm
H=1400 mm
H=1500 mm
H=1600 mm
H=1700 mm
H=1800 mm
h=600 mm
h=700 mm
h=800 mm
h=900 mm
h=1000 mm
h=1100 mm
h=1200 mm
h=1300 mm
h=1400 mm
h=1500 mm
h=1600 mm
h=1700 mm
1.80
27.80
20.43
15.64
12.36
10.01
8.27
6.95
6.03
5.60
5.23
4.90
4.61
1.90
30.98
22.76
17.42
13.77
11.15
9.22
7.74
6.60
5.91
5.52
5.17
4.87
2.00
34.32
25.22
19.31
15.25
12.36
10.21
8.58
7.31
6.30
5.81
5.45
5.13
2.10
37.84
27.80
21.29
16.82
13.62
11.26
9.46
8.06
6.95
6.10
5.72
5.38
2.20
41.53
30.51
23.36
18.46
14.95
12.36
10.38
8.85
7.63
6.64
5.99
5.64
2.30
45.39
33.35
25.53
20.17
16.34
13.50
11.35
9.67
8.34
7.26
6.38
5.90
2.40
49.42
36.31
27.80
21.97
17.79
14.70
12.36
10.53
9.08
7.91
6.95
6.16
2.50
53.63
39.40
30.17
23.83
19.31
15.96
13.41
11.42
9.85
8.58
7.54
6.68
2.6
58.00
42.62
32.63
25.78
20.88
17.26
14.50
12.36
10.65
9.28
8.16
7.23
2.7
62.55
45.96
35.19
27.80
22.52
18.61
15.64
13.32
11.49
10.01
8.80
7.79
2.8
67.27
49.42
37.84
29.90
24.22
20.01
16.82
14.33
12.36
10.76
9.46
8.38
2.9
72.16
53.02
40.59
32.07
25.98
21.47
18.04
15.37
13.25
11.55
10.15
8.99
3
77.22
56.74
43.44
34.32
27.80
22.98
19.31
16.45
14.18
12.36
10.86
9.62
3.1
82.46
60.58
46.38
36.65
29.69
24.53
20.61
17.57
15.15
13.19
11.60
10.27
3.2
87.86
64.55
49.42
39.05
31.63
26.14
21.97
18.72
16.14
14.06
12.36
10.95
3.3
93.44
68.65
52.56
41.53
33.64
27.80
23.36
19.90
17.16
14.95
13.14
11.64
H>500
300
h
300
10
350
500
(mm)
INFORMATION
▪
h=The height measured from the floor to the flare nut.
▪
H=The height measured from the floor to the bottom of the casing.
▪
For intermediate H values (i.e., when H is between 2 H values from the table),
consider the value that corresponds to the lower H value from the table. If
H=950 mm, consider the value that corresponds to "H=900 mm".
▪
In cases where H≤600 mm, h is always considered to be 600 mm, as specified in
IEC 60335-2-40:2013 A1 2016, clause GG2.
▪
For intermediate m
c
values (i.e., when m
c
is between 2 m
c
values from the table),
consider the value that corresponds to the higher m
c
value from the table. If
m
c
=2.35 kg, consider "m
c
=2.4 kg".
▪
Systems with a total refrigerant charge (m
c
) ≤1.842 kg are NOT subjected to any
requirements to the installation room.