Use the and buttons to set the desired position of the bypass valve.
Result:
No
(boiler not bypassed)
Result:
Yes
(boiler bypassed)
To perform an automatic air purge
Prerequisite:
Make sure that the leaving water temperature home page, room
temperature home page, and domestic hot water home page are turned OFF.
1
Set the user permission level to Installer. See
"To set the user permission level
104].
2
Set the air purge mode: go to [A.7.3.1]
>
Installer settings
>
Commissioning
>
Air purge
>
Type
.
3
Select
Automatic
and press .
4
Go to [A.7.3.4]
>
Installer settings
>
Commissioning
>
Air
purge
>
Start air purge
and press to start the air purge function.
Result:
Air purging will start and the following screen will be shown.
01:18
Tue
Air purge
l/min
Low
SHC
Yes
0.5
Flow rate
Speed
Circuit
Bypass
Stop
Adjust
Scroll
To interrupt air purge
1
Press and press to confirm the interruption of the air purge function.
10.4.4 To perform a test run
Prerequisite:
Make sure that the leaving water temperature home page, room
temperature home page, and domestic hot water home page are turned OFF.
1
Set the user permission level to Installer. See
"To set the user permission level
104].
2
Go to [A.7.1]: >
Installer settings
>
Commissioning
>
Test run
.
3
Select a test and press .
Example:
Heating
.
4
Select
OK
and press .
Result:
The test run starts. It stops automatically when done (±30 min). To stop it
manually, press , select
OK
and press .
INFORMATION
If 2 user interfaces are present, you can start a test run from both user interfaces.
▪
The user interface used to start the test run displays a status screen.
▪
The other user interface displays a "busy" screen. You cannot use the user
interface as long as the "busy" screen is shown.
If the installation of the unit has been done correctly, the unit will start up during
test operation in the selected operation mode. During the test mode, the correct
operation of the unit can be checked by monitoring leaving water temperature
(heating mode) and tank temperature (domestic hot water mode).
To monitor the temperature, go to [A.6] and select the information you want to
check.