7.3 ACTION AFTER EVERY ACTIVATION
●
Wait until the smoke production has ceased. Do not try to enter the affected area as you will not be
able to see through the fog.
●
Look for signs of forced entry. If you find any, or you believe that intruders are on the premises, call
the Police and wait for them to arrive. Take no further action.
●
Where there are no signs of forced entry, open all external doors and wait for the fog to start
clearing – this may take 10 to 15 minutes. Keep watch for intruders that may have been screened
by the fog.
●
As visibility returns open more doors or windows to speed up the venting process.
●
Check the fluid level for the Smoke Screen by checking the appropriate LEDs as described above.
It is recommended that the installer or Concept Smoke Screen are requested to service/replenish
the Smoke Screen if there have been 2 or more activations of the Smoke Screen.
7.4 SERVICING AND CONSUMABLE REPLENISHMENT
Installation/service engineer qualification.
Please note that it is a requirement of the standards relating to
security fogging devices that the Smoke Screen is serviced/replenished by an engineer certified by the
manufacturer. If you are unsure, ask the engineer for their certification ID card.
Smoke Screen servicing.
To ensure the Smoke Screen remains fully operational it must be regularly
serviced by a Concept Smoke Screen certified engineer. Failure to service the Smoke Screen may
invalidate the warranty.
Service intervals
. The Smoke Screen should be serviced annually by a Concept Smoke Screen certified
engineer and the following consumables should be replaced as specified:
Fluid:
Always ensure that the Smoke Screen has sufficient fluid or it will not produce smoke when
needed. The fluid consumable should be changed:
●
Every 12 months as ‘best-practise’ or, as a minimum, every 2 years.
●
If the Smoke Screen displays a Low or Empty Fluid fault in between services.
●
If there have been 2 or more activations of the Smoke Screen since the fluid was replenished.
WARNING:
Only Smoke Screen fluid should be used as other smoke fluids may cause damage to the
unit or noxious fumes.
Batteries:
The batteries should be changed:
●
At least every 2 years.
●
If the Smoke Screen displays a battery fault in between services.
WARNING: Only batteries supplied by Concept Screen should be used in the Smoke Screen
35