5.4 BATTERY MANAGEMENT
Operation
The Smoke Screen is fitted with a battery to provide power to the electronic circuits and pump (not to the
fluid heater) in the event of a mains power failure. This ensures that the Smoke Screen can provide an
effective activation for at least 1 hour after a mains power failure (further detail is on the relevant Smoke
Screen datasheet). The Smoke Screen is capable of activating in the event of a battery fault or if the
batteries are not fitted. The Smoke Screen is supplied with a set of batteries but they are not fitted on
delivery. Replacement batteries may be obtained from your Smoke Screen installer or Concept Smoke
Screen.
Removal and replacement
To remove the batteries, open the access panel on the left side of
the Smoke Screen. Slide out the old batteries and replace with new
units ensuring that the battery is upright and the contacts enter the
battery compartment first.
Battery switch
The Smoke Screen has a switch in the battery compartment to
permit the batteries to be disconnected from the system whilst
remaining in place. The delivery setting is “Off”. Select to “On” if
intending to use the battery facility.
THE SMOKE SCREEN WILL NOT FUNCTION AT ALL DURING A
MAINS POWER FAILURE IF THE BATTERIES ARE NOT FITTED OR
ARE DISABLED.