InteliMains 210 Global Guide
189
Setpoint group
Bus Left Settings
Related FW
2.0.0
Range [units]
0,0 .. 600,0 [s]
Default value
2,0 s
Alternative config
YES
Step
0,1 s
Comm object
8306
Related applications
MCB, MGCB, BTB
Description
Delay for
Bus Left Undervoltage (page 188)
and
Bus Left Overvoltage (page 188)
protection.
Bus Left < > Voltage Delay
Setpoint group
Bus Left Settings
Related FW
2.0.0
Range [units]
1 .. 150 [%] of
Nominal Voltage Ph-Ph (page 177)
Default value
10 %
Alternative config
NO
Step
1 % of
Nominal Voltage Ph-Ph (page 177)
Comm object
8446
Related applications
MCB, MGCB, BTB
Description
Threshold for Bus Left voltage unbalance.
Bus Left Voltage Unbalance
Setpoint group
Bus Left Settings
Related FW
2.0.0
Range [units]
0,0 .. 60,0 [s]
Default value
2,0 s
Alternative config
NO
Step
0,1 s
Comm object
8447
Related applications
MCB, MGCB, BTB
Description
Delay for
Bus Left Voltage Unbalance (page 189)
protection.
Bus Left Voltage Unbalance Delay
Subgroup: Bus Left Frequency Limits
Setpoint group
Bus Left Settings
Related FW
2.0.0
Range [units]
Bus Left Underfrequency (page 190)
.. 150 [%]
Default value
102,0 %
Alternative config
NO
Step
1,0 % of
Comm object
8310
Related applications
MCB, MGCB, BTB
Description
Threshold for Bus Left overfrequency.
Bus Left Overfrequency