InteliMains 210 Global Guide
184
Subgroup: Bus Right Frequency Limits
Setpoint group
Bus Right Settings
Related FW
2.0.0
Range [units]
Bus Right Underfrequency (page 184)
.. 150 [%]
Default value
102,0 %
Alternative config
NO
Step
1,0 % of
Comm object
9688
Related applications
MCB, MGCB, BTB
Description
Threshold for Bus Right overfrequency.
Bus Right Overfrequency
Setpoint group
Bus Right Settings
Related FW
2.0.0
Range [units]
50 ..
Bus Right Overfrequency (page 184)
[%]
Default value
98,0 %
Alternative config
NO
Step
1,0 % of
Comm object
9689
Related applications
MCB, MGCB, BTB
Description
Threshold for Bus Right underfrequency.
Bus Right Underfrequency
Setpoint group
Bus Right Settings
Related FW
2.0.0
Range [units]
0,0 .. 60,0 [s]
Default value
0,5 s
Alternative config
NO
Step
0,1 s
Comm object
8297
Related applications
MCB, MGCB, BTB
Description
Delay for
Bus Right Underfrequency (page 184)
and
Bus Right Overfrequency (page 184)
protection.
Bus Right < > Frequency Delay