InteliMains 210 Global Guide
110
IMPORTANT: When controller is synchronizing, there is only 2 seconds delay for breaker fail
detection.
When binary output breaker close/open is in steady state and breaker feedback is changed the breaker fail is
detected immediately (no delay).
Image 5.34 Breaker fail - breaker close/open in steady position - open
Image 5.35 Breaker fail - breaker close/open in steady position - close
When binary output breaker close/open opens there is 2 sec delay for breaker fail detection.
Image 5.36 Breaker fail - breaker close/open opens