InteliMains 210 Global Guide
458
Related FW
2.0.0
Related applications
MCB, MGCB, BTB
Comm object
77
Description
This output is active when the Bus Right voltage and frequency is within limits.
Bus Right Healthy
back to Logical binary outputs alphabetically
Related FW
2.0.0
Related applications
MCB, MGCB, BTB
Comm object
78
Description
This output is active while Bus Left failure is not detected and Bus Left voltage and frequency is within limits.
Bus Left Healthy
back to Logical binary outputs alphabetically
LBO: E
Related FW
2.0.0
Related applications
MCB, MGCB, BTB
Comm object
1250
Description
This is an output from the Exercise timer 1. This output makes it easy to make periodic tests of the gen-set
and its activation depends on the setpoints in the
subgroup. This output is
active when Timer 1 is active.
Note:
In the event that both Timers are active at the same time,
has a
higher priority than
.
Exercise Timer 1
back to Logical binary outputs alphabetically
Related FW
2.0.0
Related applications
MCB, MGCB, BTB
Comm object
1251
Description
This is an output from the Exercise timer 2. This output makes it easy to make periodic tests of the gen-set
and its activation depends on the setpoints in the
subgroup. This output is
active when Timer 2 is active.
Note:
In the event that both Timers are active at the same time,
has a
higher priority than
.
Exercise Timer 2