
InteliMains 210 Global Guide
451
Related FW
2.0.0
Related applications
MCB, MGCB, BTB
Comm object
1377
Description
This output is closed, when Binary Input 4 is active and open when Binary Input 4 is inactive. When Binary
Input 4 is used for BIN protection function then this output is closed when BIN protection alarm is in
Alarmlist.
Note:
When LBI 4 is used like protection, then state of this LBO is connected with this protection e.g.
when LBI is inactive but alarm of protection is not confirm in alarmlist, LBO is still active.
Image 8.131 Binary Input 4 Status
BIN 4 Status
back to Logical binary outputs alphabetically
Related FW
2.0.0
Related applications
MCB, MGCB, BTB
Comm object
1378
Description
This output is closed, when Binary Input 5 is active and open when Binary Input 5 is inactive. When Binary
Input 5 is used for BIN protection function then this output is closed when BIN protection alarm is in
Alarmlist.
Note:
When LBI 5 is used like protection, then state of this LBO is connected with this protection e.g.
when LBI is inactive but alarm of protection is not confirm in alarmlist, LBO is still active.
Image 8.132 Binary Input 5 Status
BIN 5 Status
Содержание InteliMains 210 BTB
Страница 169: ...PLC Setpoint 61 360 PLC Setpoint 62 361 PLC Setpoint 63 362 PLC Setpoint 64 363 InteliMains 210 Global Guide 169 ...
Страница 366: ...Log Bout 6 385 Log Bout 7 386 Date Time Time 394 Date 394 InteliMains 210 Global Guide 366 ...
Страница 494: ...InteliMains 210 Global Guide 494 Image 8 144 Configuration of OR AND block 6 back to List of PLC blocks ...