By pressing horn reset button or
It silences automatically after adjusted time
Lamp and horn test
Pressing and holding lamp test button for less than 2 s execute the basic lamp test. All LEDs light up with the
configured colour. If the button is hold longer than 2 s, an extended test is started. Every LED is tested step-by-
step in green colour and then in red colour. The horn is activated at the end of the test. After that the unit returns
to normal operation. The horn can be silenced with horn reset.
Wiring
* terminator resistor only when iGL-RA 15 is the last unit on the CAN1 bus.
Note:
The shielding of the CAN bus cable has to be grounded at one point only!
Note:
See the section
for recommended CAN bus cable type
Technical data
Power supply
8 to 36 V DC
Current consumption
0.35-0.1A (+1Amax horn output) depends on supply voltage
Protection
IP65
Humidity
85%
Storage temperature
- 30 °C to + 80 °C
Operating temperature
- 20 °C to + 70 °C
Dimensions (WxHxD)
180x120x55 mm
Weight
950 g