InteliMains 210 Global Guide
453
Related FW
2.0.0
Related applications
MCB, MGCB, BTB
Comm object
1381
Description
This output is closed, when Binary Input 8 is active and open when Binary Input 8 is inactive. When Binary
Input 8 is used for BIN protection function then this output is closed when BIN protection alarm is in
Alarmlist.
Note:
When LBI 8 is used like protection, then state of this LBO is connected with this protection e.g.
when LBI is inactive but alarm of protection is not confirm in alarmlist, LBO is still active.
Image 8.135 Binary Input 8 Status
BIN 8 Status
back to Logical binary outputs alphabetically
Related FW
2.0.0
Related applications
MCB, MGCB, BTB
Comm object
45
Description
The output controls the bus circuit breaker. Its state represents the breaker position requested by the
controller. The breaker must react within 5 seconds to a close or open command, otherwise an alarm is
issued.
Image 8.136 BTB Close command
BTB Close/Open