Panel door mounting
Note:
The final depth of the controller depends on the selected extension module - it can vary between 41 and
56 mm. Mind also a size of connector and cables (e.g. in case of RS232 connector add about another 60 mm for
standard RS232 connector and cable).
Note:
Enclosure Type rating with mounting instruction - For use on a Flat surface of a type 1 enclosure.
Note:
These devices shall be mounted in a pollution degree 2 environment enclosure having adequate strength
and thickness with acceptable spacings being provided.
Note:
The accessibility of live parts through openings in the enclosure, reliable retention of guards or barriers for
prevention of risk of electric shock, etc., shall be considered in the end product evaluation.
Note:
These devices should be used within their electrical ratings and in an ambient temperature not exceeding
70 °C, for 4 A (BOUT 1 & 2) output or 60 ºC for 5 A (BOUT 1 & 2) output.
Note:
Voltage sensing circuits shall be connected to controlled Overvoltage Category III circuits only in the end
product installation.