InteliMains 210 Global Guide
164
8.1.1 Setpoints
What setpoints are:
Setpoints are analog, binary or special data objects which are used for adjusting the controller to the specific
environment. Setpoints are organized into groups according to their meaning. Setpoints can be adjusted from
the controller front panel, PC, MODBUS, etc.
All setpoints can be protected by a password against unauthorized changes. Password protection can be
assigned to the setpoints during the configuration procedure.
IMPORTANT: Do not write setpoints repeatedly (e.g. power control from a PLC by repeated writing
of baseload setpoint via Modbus). The setpoints are stored in EEPROM memory, which can be
overwritten up to 10
5
times without risk of damage or data loss, but it may become damaged, when
the allowed number of writing cycles is exceeded.
List of setpoint groups
Group: Alternate Configuration
For full list of setpoints go to the chapter