529
Related applications
MCB, MGCB, BTB
Description
This alarm evaluates the Bus Left phase voltage in phases. The following setpoints
are related to it:
Bus Left Undervoltage (page 188)
Bus Left < > Voltage Delay (page 189)
Note:
Alarm is active only in case the setpoint
is
set to 3Ph4Wire.
back to List of alarms level 2
Alarm Type
Breaker open
Alarmlist message
No
Alarm evaluated
All the time
Related applications
MCB, MGCB, BTB
Description
This alarm evaluates the Bus Left voltage between phases L3 a L1. The following
setpoints are related to it:
Bus Left Overvoltage (page 188)
Bus Left < > Voltage Delay (page 189)
Note:
Alarm is active only in case the setpoint
is
set to 3Ph3Wire or High Leg D or SplitPhase.
Bus Left L3L1 Overvoltage
back to List of alarms level 2
Alarm Type
Breaker open
Alarmlist message
No
Alarm evaluated
All the time
Related applications
MCB, MGCB, BTB
Description
This alarm evaluates the Bus Left voltage between phases L3 a L1. The following
setpoints are related to it:
Bus Left Undervoltage (page 188)
Bus Left < > Voltage Delay (page 189)
Note:
Alarm is active only in case the setpoint
is
set to 3Ph3Wire or High Leg D or SplitPhase.
Bus Left L3L1 Undervoltage
back to List of alarms level 2
Alarm Type
Breaker open
Alarmlist message
No
Alarm evaluated
All the time
Bus Left L1 Overvoltage