InteliMains 210 Global Guide
117
Short period mode
Set-up via InteliConfig
To set-up timer via InteliConfig go to the setpoint ribbon, setpoint group scheduler and setpoint
Timer 1 Setup
.
Note:
First of all function of timer has to be adjusted via setpoint
Image 5.43 Short period mode - InteliConfig
In timer mode select Repeat. In repetition type select Short period. In timer settings adjust date and time of first
occurrence of timer. Also adjust the duration of each occurrence of timer. Than select the interval of repetition
(shorter than 1 day).
Example:
On image example first start of timer will be 1/1/2016 at 12:00. Duration will be 1 hour. Timer will
be again activated every 4th hour for 1 hour.
Set-up via controller interface
In controller go to the Scheduler setpoint group. Select the function of timer via
setpoint. Than go to
Timer 1 Setup
and press enter button. In
setpoint select
Repeated mode. Than adjust
Timer 1 First Occur. Date (page 251)
Timer 1 First Occur. Time (page 251)
and
. In setpoint
select Short Period and adjust
(interval of repetition).
Note:
Use left and right buttons to move between timer setpoints.
5.4.14 Analog switches
There are logical analog function dedicated for analog switches. Each analog switch has setpoints for level ON
and level OFF and logical binary output.