InteliMains 210 Global Guide
205
Setpoint group
Synchronisation
Related FW
2.0.0
Range [units]
0,0 .. 100,0 [%]
Default value
10,0 %
Alternative config
NO
Step
0,1 %
Comm object
8650
Related applications
MCB, MGCB, BTB
Description
This setpoint adjusts maximum difference between Bus Right and Bus Left voltage in respective phases for
synchronization.
Voltage Window
Setpoint group
Synchronisation
Related FW
2.0.0
Range [units]
0 .. 90 [°]
Default value
10 °
Alternative config
NO
Step
1 °
Comm object
8652
Related applications
MCB, MGCB, BTB
Description
This setpoint adjusts the maximum absolute value of difference between actual phase angle between the
Bus Right and Bus Left voltages for synchronization.
Phase Window
Setpoint group
Synchronisation
Related FW
2.0.0
Range [units]
0,0 .. 25,0 [s]
Default value
0,3 s
Alternative config
NO
Step
0,1 s
Comm object
8653
Related applications
MCB, MGCB, BTB
Description
The period of time that the phase angle difference must be within
and voltage
difference within
before the breaker is closed.
Dwell Time
Setpoint group
Synchronisation
Related FW
2.0.0
Range [units]
-0,50 .. 0,50 [Hz]
Default value
-0,25 Hz
Alternative config
NO
Step
0,01 Hz
Comm object
14798
Related applications
MCB, MGCB, BTB
Description
Slip frequency for slip synchronization (
Synchronization Type (page 204)
= Slip Synchro).
Slip Frequency