InteliMains 210 Global Guide
29
3 phase application:
Image 4.1 3 phase application
It is necessary to ensure that potential difference between current COM terminal and battery “-” terminal is
maximally ± 2 V. Therefore is strongly recommended to interconnect these two terminals together.
Split phase application:
Image 4.2 Split phase application
IMPORTANT: The second phase of split phase connection is connected to the terminal, where is
normally connected the third phase.