InteliMains 210 Global Guide
198
Subgroup: Start/Stop Timing
Setpoint group
Power Management
Related FW
2.0.0
Range [units]
0 .. 3 600 [s]
Default value
5 s
Alternative config
NO
Step
1 s
Comm object
8492
Related applications
MCB, MGCB
Description
This setpoint adjusts the delay for starting the next gen-set after the reserve has dropped below the reserve
for start.
#Next Engine Start Delay
Setpoint group
Power Management
Related FW
2.0.0
Range [units]
0 .. 3 600 [s]
Default value
20 s
Alternative config
NO
Step
1 s
Comm object
8494
Related applications
MCB, MGCB
Description
This setpoint adjusts the delay for stopping the gen-set after the reserve has risen above the reserve for
stop.
#Next Engine Stop Delay
Setpoint group
Power Management
Related FW
2.0.0
Range [units]
0 .. 600 [s]
Default value
60 s
Alternative config
NO
Step
1 s
Comm object
8495
Related applications
MCB, MGCB
Description
This setpoint is used to adjust how long the particular gen-set will suppress it's own Slow stop alarm to give
chance to another gen-set to start and replace the defective one.
Note:
If there isn't any available gen-set to start, the alarm is not suppressed.
Note:
This function is not supported in BTB application.
#Slow Stop Delay