Alarm Type
Warning
Alarmlist message
Wrn Overload
Alarm evaluated
All the time
Related applications
MCB, MGCB, BTB
Description
The alarm is issued when the Bus Left power is over the limit for time period longer
than the delay. The following setpoints are related to it:
adjusts the overload limit.
Overload Del adjusts the delay.
Wrn Overload
back to List of alarms level 1
Alarm Type
Warning
Alarmlist message
Synchronization Fail
Alarm evaluated
During synchronization
Related applications
MCB, MGCB, BTB
Description
This alarm is issued when bus left is synchronizing to the bus right or vice versa,
via BTB and
Synchronization Timeout (page 204)
gets elapsed.
Synchronization Fail
back to List of alarms level 2
Alarm Type
Warning
Alarmlist message
Bus Measurement Error
Alarm evaluated
All the time
Related applications
MCB, MGCB, BTB
Description
The alarm is issued when the voltage on the bus is out of limits for 20 seconds
under these conditions:
MCB application:
MCB is closed in AUTO mode
Any GCB in the same control group was closed
MGCB application:
MCB and MGCB are closed in AUTO mode
Any GCB in the same control group was closed. MGCB closing is blocked
BTB application:
BTB feedback was closed in AUTO mode
Any GCB in power management group (on CAN bus) was closed.
BTB closing is blocked
Bus Measurement Error