178
Subgroup: Frequency settings
Setpoint group
Basic settings
Related FW
2.0.0
Range [units]
45 .. 65 [Hz]
Default value
50 Hz
Alternative config
YES
Step
1 Hz
Comm object
8278
Related applications
MCB, MGCB, BTB
Description
Nominal system frequency (usually 50 or 60 Hz).
Note:
To lock this setpoint against editing you also have to lock setpoint
Nominal Frequency 2 (page 296)
and
Nominal Frequency 3 (page 298)
.
Nominal Frequency
Subgroup: Controller settings
Setpoint group
Basic settings
Related FW
2.0.0
Range [units]
OFF / MAN / AUTO / TEST [-]
Default value
OFF
Alternative config
NO
Step
[-]
Comm object
8315
Related applications
MCB, MGCB, BTB
Description
This setpoint can be used for changing the Controller mode remotely, e.g. via MODBUS. Use the mode
selector on the main screen for changing the mode from the front panel. Use mode selector in the control
window for changing the mode from InteliConfig.
Controller mode