Corner-Grounded Delta
Split Phase Delta
Three phase voltage measurement L1,L2,L3 with 120° phase shift
No neutral is available 3x CT (Current Transformer)
High Leg D
High Leg Delta connection
Three phase voltage measurement L1,L2,L3
3x CT (Current Transformer)
3Ph4Wire
Grounded Star (Grounded Wye) connection – 3PY
Three phase voltage measurement L1,L2,L3 with 120° phase shift
3x CT (Current Transformer)
Note:
This value is used when binary input
is active.
Subgroup: Configuration 3
Setpoint group
Basic settings
Related FW
2.0.0
Range [units]
45 .. 65 [Hz]
Default value
50 Hz
Alternative config
YES
Step
1 Hz
Comm object
15197
Related applications
MCB, MGCB, BTB
Description
Nominal system frequency (usually 50 or 60 Hz).
Note:
This value is used when binary input
is active.
Nominal Frequency 3
Setpoint group
Basic settings
Related FW
2.0.0
Range [units]
80 .. 20 000 [V]
Default value
231 V
Alternative config
YES
Step
1 V
Comm object
12054
Related applications
MCB, MGCB, BTB
Description
Nominal system voltage (phase to neutral).
Note:
This value is used when binary input
is active.
Nominal Voltage Ph-N 3