Digital fire detection control panel
LYON REMOTE PLUS
80
FIRE PROTECTION MANUFACTURER
C / Compositor Wagner, 8 –P.I. Can Jardí 08191 - RUBÍ (Barcelona) ESPAÑA.
Tlf.: +34 935 862 690 –
REMOTE CONECTION:
It allows configuring the following communication parameters of the REMOTE card in the ethernet network.
Activate/Deactivate the communications with REMOTE CARD.
IP: Defines the IP address of the REMOTE card in the internal network. By default
192.168.0.254.
PORT: Defines the port of the REMOTE card. The server / router must be configured to
allow communication between the REMOTE card and the external network. By default the
value is 80.
MASK: Mask of the server / router that differentiates the IP addresses of the internal and
external network. Based on the IP address of the server / router, the "0" values identify the
internal addresses. By default, the value of the mask is 255.255.255.0.
GATEWAY: IP address of the server / router. By default the value is 192.168.0.50.
DHCP: allow automatic configuration of IP, PORT and MASK.
UMIP: Acronym for "Update My IP". With the activation of this function, it is allowed to
communicate with the REMOTE card of the central from the web "www.l-remote.com"
automatically without needing to know the IP address of the server / router.
SERIAL NUMBER: It is the serial number of the REMOTE card needed to identify it on
the web "www.l-remote.com".
3.2.3.10.- Stop Sounder Function……………………………………………….…………..Menu_16
ACTIVATION:
CONTINUOUS: "Stop Sounder" continues active after re-start up of the control panel.
RESET: "Stop Sounder" is automatically desactivated after re-start up of the control panel.
PERFORMANCE:
CONTINUOUS: "Stop Sounders" continues active although new signal alarm arrives to
control panel.
EVENT: "Stop Sounders" is deactivated when new signal alarm is received to control
panel.
VIEW SET UP: It is shown selection of "ACTIVATION" and "PERFORMANCE”.