Digital fire detection control panel
LYON REMOTE PLUS
73
FIRE PROTECTION MANUFACTURER
C / Compositor Wagner, 8 –P.I. Can Jardí 08191 - RUBÍ (Barcelona) ESPAÑA.
Tlf.: +34 935 862 690 –
of a relay to different points located in different loops and centers within the system.
Furthermore, the sub-lists are related to each other by the logical command AND (&)
and OR (/). The AND (&) command means that the trigger conditions of that sub-list
must be given with that of the next one. The OR (/) command means that the trigger
conditions of that sub-list must be given "or" that of the next one.
Below are some examples.
Case 1:
Relay Number Loop number First point Last point
R E L A Y : 1
L A B E L :
1
C T R L : 0 1
L O O P : 0 1
A L R M : 3
P N T S : 0 0 1 : 0 0 9
/
2
C T R L : 0 0
L O O P : 0 0
A L R M : 0
P N T S : 0 0 0 : 0 0 0
/
3
C T R L : 0 0
L O O P : 0 0
A L R M : 0
P N T S : 0 0 0 : 0 0 0
/
List (sub-list) Control_Panel Alarms Logic (OR , AND)
In this case, relay 01 will be activated when there are more than 3 sensors in alarm state from 9 sensors that are
present in the LOOP_01 in Control_Panel_01
Case 2:
R E L A Y : 1
L A B E L :
1
C T R L : 0 1
L O O P : 0 1
A L R M : 1
P N T S : 0 0 1 : 0 0 1
&
2
C T R L : 0 0
L O O P : 0 0
A L R M : 1
P N T S : 0 0 5 : 0 0 5
&
3
C T R L : 0 0
L O O P : 0 0
A L R M : 0
P N T S : 0 0 9 : 0 0 9
/
In this case the RELAY_01 will be activated by Control_Panel_01 from LOOP_01 when sensor 1,5 and 9 are all
of them in alarm state, and our relay may be in that loop or another.
Very important
to notice is the logic
operator “OR”
that should
ALWAYS
be at the
end of any list (sub-list),
otherwise the
relay
01 will
never
be
activated
.
Case 3:
R E L A Y : 1
L A B E L :
1
C T R L : 0 1
L O O P : 0 1
A L R M : 1
P N T S : 0 0 1 : 0 0 1
&
2
C T R L : 0 2
L O O P : 0 1
A L R M : 1
P N T S : 0 0 5 : 0 0 5
&
3
C T R L : 0 3
L O O P : 0 1
A L R M : 1
P N T S : 0 0 9 : 0 0 9
/
In this last scenario, the “RELAY 1” will be activated only when all 3sensors defined in different Control_Panels
in network are in alarm state.
VIEW CONFIGURATION: View the configuration of the relay and all its
parameters.
R E L A Y :
R e l a y
M a n e u v e r
R e l a y
0 0 2
M D A 2 Y
M a n e u v e r
L o o p :
0 0 2
P o i n t : 0 0 3
D A Y
D e t e c t o r : Y e s
C a l l : Y e s
D e l a y :
0 0
N I G H T
D e t e c t o r : Y e s
C a l l : Y e s
VIEW DELAY LISTS: View the list of points configured for the relay.