Digital fire detection control panel
LYON REMOTE PLUS
70
FIRE PROTECTION MANUFACTURER
C / Compositor Wagner, 8 –P.I. Can Jardí 08191 - RUBÍ (Barcelona) ESPAÑA.
Tlf.: +34 935 862 690 –
3.2.3.2.- Label points.
O
ption 1 of the SYSTEM CONFIGURATION menu. We will have to introduce the loop and element
number to label. This is an option that allows us to label each element of the system, that is to say, to give
each point a description that gives us the information necessary to physically locate it in the installation.
The label can have a maximum of 20 characters. This is the screen that appears during the labelling
process:
E N T E R
T E X T :
O F F I C E
Z O N E
1
M E N U - > C O P Y
R E S E T - > P A S T E
E N T E R - > A C C E P T
3.2.3.3.- Configure. ........................................................................................................................Menu_9
Option 2 of the SYSTEM CONFIGURATION menu.
3.2.3.3.1. - Loop configuration. .................................................................................................Menu_17
In this menu we have the possibility of configuring all the parameters related to the element of a loop such
as: to assign the element numbers, to detect the elements, to configure sensitivity, etc.
Within the LOOP CONFIGURATION menu we have three important submenus that are:
SENSITIVITY OF A TYPE: This submenu allows us to vary the sensitivity of all the sensors
configured in the loop according to the type. Sensitivity has three levels HIGH, AVERAGE and
LOW (all the sensors come with average sensitivity).
BLINK: This submenu allows us to enable/disable the blinking leds of all the elements configured
in the loop.
POINT CONFIGURATION: In this submenu we will be able to detect the elements that are
connected to the loop and to assign a point number to them. Within this submenu we have seven
submenus: