Digital fire detection control panel
LYON REMOTE PLUS
27
FIRE PROTECTION MANUFACTURER
C / Compositor Wagner, 8 –P.I. Can Jardí 08191 - RUBÍ (Barcelona) ESPAÑA.
Tlf.: +34 935 862 690 –
1.5.4.7-Module to connect 32 detectors / 10 manual call points (KMAY32)
Microprocessed addressable module (with short-circuit
insulator) which is installed as one more element in the
loop.
This module allows the connection of conventional
detectors and/or alarm call points in an algorithmic-
addressable fire detection system, acting as a bridge
between an algorithmic-addressable control panel and a
conventional system.
Up to a maximum of 10 conventional alarm call points can be
installed on the strip of “Zone C”. The “Zone D” strip allows a
maximum of 32 temperature detectors (A30XT, A30XV) or 32
components between smoke detectors (A30XH, A30XHS) and
conventional alarm call points. Both strips supervise the line using
a 4K7end-of-line resistor. It thus indicates the status of the open
line, crossed line, detector alarm or alarm call point alarm.
It has a microswitch for setting the area thresholds;
- Open line threshold (pin microswitch 1-2).
- Detector alarm triggered threshold (pin microswitch 3-4).
- Alarm call point triggered threshold (pin microswitch 5).
The blinking of the red transparent LED indicates communication
with the control panel, and if it stays on in indicates the status of
the alarm of a detector or of a alarm call point connected to that
module.
This module has an output for the activation of a remote pilot,
which is activated when it is in alarm state.
This module is powered by the loop connection and requires a
24V auxiliary power supply to power the areas, said voltage is supervised by the microcontroller.
Rectangular boxes made of heat-resistant ABS are available on order.
Figure 9
. KMAY32 wiring diagram