Digital fire detection control panel
LYON REMOTE PLUS
38
FIRE PROTECTION MANUFACTURER
C / Compositor Wagner, 8 –P.I. Can Jardí 08191 - RUBÍ (Barcelona) ESPAÑA.
Tlf.: +34 935 862 690 –
1.5.5.2. Operation and Configuration..........................................................................................Menu_25
The repeaters display all the information about alarms, disconnections, relay actuations and faults.
Once the repeaters have been connected, they must then be configured in the control panel by entering the
number of each repeater to be configured.
To do this, follow this sequence in the control panel: Menu (access code 27)
4.
System setup (access
code 9000)
8
Communications
1-
Repeater network
2 -
Configure repeaters.
Control_Panel_Menu
After configuring the control panel, a number must then be assigned to each repeater. This must be the
same as the one which was configured in the control panel. To do this, follow this sequence in the
corresponding repeater:
Menu (access code 27)
1.
System setup (access code 9000)
3
.Address number.
Repeater_Menu
When configuration has been completed, the general system reset must be performed from the control
panel. To do this, follow this sequence: Menu (access code 27)
8-
General reset.
Control_Panel_Menu