1.5.4.9- Loop isolator (KABY)
The kaby element installed as another element inside the loop (It is
not addressable - There is not need to configure this element).
This is a protection element that is connected into the detection
loop, with the aim of isolating stretches with crossed line
failures, and allowing therefore the rest of the loop to operate
normally.
It is supplied installed inside of a high base. This assembly allows
having it in the same place as the sensor, making easy the
connection of the loop wiring.
The base has two stickers in the outer side with the word
“KABY”
to allow easy recognition.
The element is feed from the loop connection.
The
KABY
is conformant with EN 54-17 with the conformity mark awarded by AENOR.
Note: To determine the number of KABY devices that can be installed in a loop consult the devices limit
per control panel table (Chapter 1.5)
IMPORTANT The polarity in the KABY is showned in figure 11
Figure 11.
KABY wiring diagram