FIRE PROTECTION MANUFACTURER
C / Compositor Wagner, 8 –P.I. Can Jardí 08191 - RUBÍ (Barcelona) ESPAÑA.
Tlf.: +34 935 862 690 –
3.2.3.3.7- Added Delay Setup.................................................................................................Menu_9
This option is activated when it is introduced a time between 1" to 9 min 59".
When the
first
signal alarm is received, control panel actives corresponding programmed
delays
.
If operator press "
Silence Buzzer
" before programmed delay time is finished, all the relays (including the
sounder relay output in control panel) are additionally delayed with the value "
Additional delay
". In this
way, operator is allowed to investigate alarm.
If at any time during the delays a
second alarm
occurs (without the need to press the stop buzzer) in the
control panel, all the relays associated with the elements of alarm are
triggered immediately
.
3.2.3.3.8- Fast Trigger Zone...................................................................................................Menu_9
The alarm signal input of any element defined in the zone introduced in this option makes immediately
activation of all control panel relays.
3.2.3.3.9- Send Zones to Repeaters........................................................................................Menu_9
This option allows sending the configured zones to the repeaters, if not executed the repeaters will only
indicate the label of the point.
3.2.3.4- Update date and time .............................................................................................Menu_10
Within this menu we have two options, CHANGE DATE and CHANGE TIME. With the cursors we will
be able to update the fields for both options.
3.2.3.5.- Day/ Night timetable............................................................ .................................Menu_11
The day/night mode serves to configure the activations of relays since they can have a different operation
for day and night. The day mode can be activated or deactivated independently for the different days of the
week.
DAY TIME START: The control panel will request the start time for the day mode.
DAY TIME END: The control panel will request the end time for the day mode.
PROG. NIGHT MODE DAYS: This option allows us to configure the control panel night
mode for the whole 24 hours of a day.
DELETE NIGHT MODE PROG.: This option deletes the configuration described in the
previous paragraph
PROGRAMMING SUMMARY: This option shows us the configuration of the night mode