Digital fire detection control panel
LYON REMOTE PLUS
95
FIRE PROTECTION MANUFACTURER
C / Compositor Wagner, 8 –P.I. Can Jardí 08191 - RUBÍ (Barcelona) ESPAÑA.
Tlf.: +34 935 862 690 –
3.5.-Assign a number to Point
Confirm with the
ENTER
key.(Menu(code 27)
4.-System setup (code 9000)
2.-Configure
1.Loop
configuration
3.-Set up Loop Points
3.- Assign Point number)
This option assigns a loop and an order number within the loop to each element.
Important:
In order to proceed with this operation, the installer must have made written note of the programming number of
each of the sensors and the loop in which they are installed.
Firstly, you will be asked for the programming number of the corresponding Point, confirmed with the
ENTER
key. Secondly, you will be asked for the assigned Point number, confirmed with the
ENTER
key
.
4.-Programming verification process
It is always recommended to check that programming has been performed correctly.
Monitor
This function is number 1 on the first menu. Select with the ENTER key.
The control panel will ask first for the loop number and then the point number.