Digital fire detection control panel
LYON REMOTE PLUS
94
FIRE PROTECTION MANUFACTURER
C / Compositor Wagner, 8 –P.I. Can Jardí 08191 - RUBÍ (Barcelona) ESPAÑA.
Tlf.: +34 935 862 690 –
3.3-Configure Loop
By selecting option
1 Loop Configuration
the option will be the first to appear. Confirm with the
ENTER
key.
You will be asked for the number of the loop to be configured.
The following menu with 3 options will appear on the display:
3.4.-Loop Configuration
The first step is to configure the elements of the loop so that the control unit recognizes all the Elements that are
connected to each of the loops.
By selecting option
3 Set up loop Points
the option will be the first to appear. Confirm with the
ENTER
key.
The following menu with 7 options will appear on the display:
By selecting option
2
Loop points Search
the option will be the first to appear. Confirm with the
ENTER
key.
Confirm with ENTER,(Menu(code 27)
4
.-System setup
2
.-Configure
1
.-Loop configuration
3
.-Set Up
Loop Points
2
.-Loop points Search)
This function passes all the programming numbers to the control unit memory and, after a few seconds, the total
number of elements that have been configured in the loop will appear on the display and how many there are of
each type.
This search will take approximately 80 seconds.
Check that the information displayed is correct.
Important note
:
This step must be performed for each of the installed loops.
It must be done even if there are no elements connected to the loop
.