Using a computer and an Ethernet cable, you can communicate with the TV-MPCXP through a web browser to:
•
View the controller's Module Status report
•
View/change controller and network settings. Changes take effect immediately.
•
Troubleshoot
•
Use BACnet/IP Service Port to access the i-Vu® application or a touchscreen device. See
To communicate
through the BACnet/IP Service Port network
(page 31).
1
Connect an Ethernet cable from a computer to the controller as shown below.
2
Turn off the computer's Wi-Fi if it is on.
3
If your computer uses a static IP address, use the following settings:
○
Address: 169.254.1.x, where x is 2 to 7
○
Subnet Mask: 255.255.255.248
○
Default Gateway: 169.254.1.1
4
If it uses a DHCP address, leave the address as it is.
5
Open a web browser on the computer.
6
Navigate to http://local.access or http://169.254.1.1 to see the Service Port controller setup pages.
NOTE
The first time you access the controller in the i-Vu® interface after you have changed settings through the
Service Port, be sure to upload the changes to the system database. This will preserve those settings when you
download memory or parameters to the controller.
ModStat tab
This tab provides the controller's Module Status report that gives information about the controller and network
communication status. See
Appendix - Module Status field descriptions
(page 59).