![Carrier TruVu MPC Скачать руководство пользователя страница 26](http://html1.mh-extra.com/html/carrier/truvu-mpc/truvu-mpc_installation-and-startup-manual_2562393026.webp)
Addressing the TV-MPCXP
TruVu™ MPC Processor
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
22
Configuring BACnet Device Instance and network number
The TV-MPCXP controller must have a unique Device Instance and Name. These BACnet addresses are
automatically generated and usually do not require modification. However, sometimes you need to override the
automatic addressing assignments.
Autogenerated addressing scheme:
The TV-MPCXP's rotary address setting determines the automatic BACnet addressing scheme for the connected
Open network.
Legend
16 = Carrier's BACnet Vendor ID
xxx = TV-MPCXP's rotary switch address (See NOTES below.)
yy = Controller's rotary switch address (ARCNET/MSTP MAC address)
For the TV-MPCXP:
•
BACnet Device Instance Number = (IP network number x 100) + rotary switch address
•
BACnet Device Instance Name = the name "device" + the Device Instance
•
BACnet IP Network Number = 1600
•
BACnet ARC/MSTP Port S1 Network Number = ((IP network rotary switch address) x 10)
•
Port S1 MSTP MAC Address = 0 by default (user configurable)
•
Port S1 ARCNET Address = 254 by default (user configurable)
•
BACnet MSTP Port S2 Network Number = ((IP network rotary switch address) x 10) +3
•
Port S2 MSTP MAC Address = 0 by default (user configurable)
For the Open controllers connected to the TV-MPCXP
•
BACnet MSTP Device Instance Number = BACnet MSTP Network yy
•
BACnet ARCNET Device Instance Number = BACnet ARCNET Network yy
•
BACnet MSTP Device Instance Name = the name "device" + Device Instance
•
BACnet ARCNET Device Instance Name = the name "device" + Device Instance
•
BACnet MSTP or ARCNET MAC Address = yy
•
BACnet MSTP Network Number = 161xx (learned from the router, defaults to 16101 if no TV-MPCXP is
operating)
NOTES
•
Do not configure the rotary switches on the TV-MPCXP to a number greater than 127 unless Port S1 is
enabled for ARCNET. Doing so will not allow the i-Vu® server to discover the TV-MPCXP.
If you change the TV-MPCXP's switches or jumpers, you must cycle its power for the changes to take effect.
•
If the BACnet automatic settings need to be changed, see
To communicate through the Local Access port
(page 47).