To attach I/O expanders
TruVu™ MPC Processor
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
9
To add inputs or outputs to the TV-MPCXP, you can attach up to 9 TruVu
TM
MPC I/O expanders and/or 6 MPC
Open XPIO expanders, but no more than 9 expanders total. Each expander must have a unique address (1
through 9) set on its rotary switch. An MPC Open XPIO expander's address must be in the range from 1 to 6.
See:
TruVu
TM
MPC I/O expander configurations
(page 9)
To attach TruVu
TM
MPC I/O expanders
(page 13)
To attach MPC Open XPIO expanders
(page 14)
The expander's
Installation and Start-up Guide
TruVu MPC I/O expander configurations
The expanders' outputs return to their unconfigured state if they are removed from the program or the program is
deleted from the controller. Also, outputs time out and return to their unconfigured or off state after two minutes
of inactivity. The unconfigured state results in:
•
Not running control programs that are due to download
•
Losing power to the controller, but not the expander
NOTE
This does not apply to outputs that have been locked in the i-Vu® application.
The TruVu
TM
MPC I/O expander can be connected to the TV-MPCXP in one of the following ways:
•
Directly-connected to the I/O bus edge connector that provides power and communication