To set up the controller through the Service Port
TruVu™ MPC Processor
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
50
BACnet Secondary IP Net
Number
If the TV-MPCXP has two BACnet/IP networks communicating on the Gig-E port,
enter the second IP network number in this field.
If the TV-MPCXP is behind a NAT router and there is a second network with
BACnet/IP devices behind the NAT router, enter the second network number in
this field to logically connect the TV-MPCXP to the devices on the second network.
P rivate
s ide
BACnet
router
Public
s ide
N
A
T
R
Controller
Sec ondary I P
network
C
BACnet Secondary UDP Port
If the TV-MPCXP has two BACnet/IP networks communicating on the Gig-E port,
enter the port number that the i-Vu® application will use for BACnet
communication. This port must be different than the
BACnet UDP Port
.
Ethernet Port
MAC Address
A factory assigned Ethernet MAC Address for the
Gig-E
port.
BACnet Network Number
Specify a number for the BACnet/Ethernet network or set to 0 if the port is not
used.
Port S1
End of Network
Indicates status of the controller's
End of Net?
switch.
Active Protocol
Indicates status of the controller's Port S1 rotary switch.
0=Disabled
1=MS/TP
2=ARCNET
3=Modbus
Address
The address that is set on the three rotary switches. See
To set the Port S1
address and baud rate
(page 21).
ARCNET Baud Rate
156000
MSTP Autobaud
Select
Yes
to enable this slave device to automatically receive its baud rate from
a master on the network that has the fixed baud rate.
MSTP Baud Rate
Set this to a baud rate that all other devices on the MS/TP network are set to.
MSTP Max Master
To increase MS/TP performance, enter the highest address used on the MS/TP
network for a master controller. This number must be less than or equal to 127.
MSTP Max Info Frames
This is the maximum number of information messages a controller may transmit
before it must pass the token to the next controller. Valid values are 1 to 255.
TIP
Set
Max Info Frames
to a number in the range 20 to 100 so that the
router does not become a bottleneck for traffic being routed from a high-speed
network to the slower MS/TP network.
BACnet Network Number
Select:
Disable Routing
if Port S1 is not used.
Autogenerated
to have the network number for Port S1 automatically set to a
number equal to ((IP network rotary switch address) x 10).
Assigned
to enter a specific number.