To set up the controller through the Service Port
TruVu™ MPC Processor
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
51
Port S2
End of Network
Indicates status of the controller's
End of Net?
switch.
Active Protocol
Shows one of the following:
•
Modbus
if enabled on the
Modbus
tab
•
BACnet/MSTP
if you enter a
BACnet Network Number
below for an MS/TP
network
•
Disabled
if neither of the above have been done
Address
The controller’
s unique address on the MS/TP network.
MSTP Autobaud
Select
Yes
to enable this slave device to automatically receive its baud rate from
a master on the network that has the fixed baud rate.
MSTP Baud Rate
Set this to a baud rate that all other devices on the MS/TP network are set to.
MSTP Max Master
To increase MS/TP performance, enter the highest address used on the MS/TP
network for a master controller. This number must be less than or equal to 127.
MSTP Max Info Frames
This is the maximum number of information messages a controller may transmit
before it must pass the token to the next controller. Valid values are 1 to 255.
TIP
Set
Max Info Frames
to a number in the range 20 to 100 so that the
router does not become a bottleneck for traffic being routed from a high-speed
network to the slower MS/TP network.
BACnet Network Number
Select:
Disable Routing
if Port S2 is not used.
Autogenerated
to have the network number for Port S2 automatically set to a
number equal to ((IP network rotary switch address) x 10) + 3.
Assigned
to enter a specific number.
Home Network
This is typically the network that is communicating with the building automation
system's application. This sets the BACnet Address of the Device object.
Modbus tab
If the controller will be used with Modbus devices, see the
Modbus Integration Guide
for information on using this
tab.
Security tab
BACnet Firewall
If your BACnet Firewall configuration in the i-Vu® interface did not include the i-
Vu® server IP address, thus blocking communication with the i-Vu® server, you
can disable the controller's BACnet Firewall on the controller setup
Security
tab.
NOTE
You can enable the BACnet Firewall only in the i-Vu® interface.