Addressing the TV-MPCXP
TruVu™ MPC Processor
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
21
To set the Port S1 address and baud rate
The address should be in one of the following ranges based on the port's use.
Port address
•
For ARCNET, the range is 1 to 254.
•
For MS/TP, the range is 0 to 127.
•
For Modbus, the range is 1 to 247.
For MS/TP, set up autobaud or the port's baud rate
1
On the controller setup
BACnet
tab under
Port S1
, select the
MSTP Baud Rate
or select
Yes
for
MSTP
Autobaud
. The default is 76,800 bps.
NOTES
○
See
To set up autobaud
(page 18) for details.
○
If not using autobaud, enter the identical baud rate for all devices on the same MS/TP network segment.
2
Click
Save
.
Modbus
For Modbus, see the
Modbus Integration Guide
.
To set the Port S2 address and baud rate
For MS/TP, set up autobaud or the port's baud rate
1
On the controller setup
BACnet
tab under
Port S2
, type the address in the
MSTP Address
field. The address
must be in the range 0 to 127.
2
Select the
MSTP Baud Rate
or select
Yes
for
MSTP Autobaud
. The default is 76,800 bps.
NOTES
○
See
To set up autobaud
(page 18) for details.
○
If not using autobaud, enter the same baud rate for all devices on the MS/TP network.
3
Click
Save
.
Modbus
For Modbus, see the
Modbus Integration Guide
.