Wiring for communications
TruVu™ MPC Processor
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
28
To connect the TV-MPCXP to the Ethernet
Connect an Ethernet cable to the Gig-E Ethernet port.
NOTE
If your system has controllers on different IP subnets separated by an IP router, you must configure one
controller on each subnet as a BACnet Broadcast Management Device (BBMD). Do not configure more than one
BBMD per subnet as this may cause circular routes. See
To set up BACnet Broadcast Management Devices
(BBMDs)
(page 23).
To wire to a BACnet/ARCNET network
1
Turn
off
the TV-MPCXP's power.
2
Check the communications wiring for shorts and grounds.
3
Connect the communications wiring to
Port S1
’s screw terminals labeled
Net +
,
Net -
, and
Shield
.
NOTE
Use the same polarity throughout the network segment.
4
If the controller has a
Port S1 Configuration
rotary switch, set it to 2.
5
If the TV-MPCXP is at either end of a network segment, set the port's
End of Net
switch to
Yes
.
NOTE
The controller’s
End of Net
switch applies network termination and bias. See the
Open Controller
Network Wiring Guide.
6
Turn on the controller's power.
7
To verify communication with the network, get a Module Status report in the i-Vu® interface for a controller
on the ARCNET network.
NOTE
This step requires that you have discovered and uploaded the controller in the i-Vu® application.
Содержание TruVu MPC
Страница 66: ......
Страница 67: ...CARRIER CORPORATION 2021 Catalog No 11 808 691 01 9 20 2021...