What
is the TruVu™ MPC Processor?
TruVu™ MPC Processor
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
5
Compliance
United States of America:
FCC compliant to Title CFR47, Chapter 1, Subchapter A, Part 15, Subpart B, Class
A; UL Listed to UL 916, PAZX, Energy Management Equipment
Canada:
Industry Canada Compliant, ICES-003, Class A
cUL Listed UL 916, PAZX7, Energy Management Equipment
Europe:
Mark
EN50491-5-2:2009; Part 5-2: EMC requirements for HBES/BACS used in
residential, commercial and light industry environment
EN50491-3:2009, Part 3: Electrical safety requirements for Home and Building
Electronic Systems (HBES) and Building Automation and Control Systems (BACS)
Low Voltage Directive: 2014/35/EU
RoHS Compliant: 2015/863/EU
Australia and New Zealand:
C-Tick Mark, AS/NZS 61000-6-3
Zone sensors
You can wire ZS sensors and/or a Wireless Adapter that communicates with wireless sensors to the TV-MPCXP's
Rnet port. You can have up to 15 ZS and/or wireless sensors.
NOTES
•
A control program can use no more than 5 ZS sensors, so you must use multiple control programs if your
Rnet network has more than 5 sensors.
•
ZS and wireless sensors can share the Rnet
with an Equipment Touch or TruVu™ ET Display.
CAUTION
Rnet power
The Rnet port provides 12 Vdc at 62.5 mA maximum that can be used to power zone sensors. When determining
which devices to put on the Rnet, verify that the total current draw of the sensors does not exceed the controller's
Rnet power. See the sensor's I
nstallation and Start-up Guide
to determine the power required.