Rotary switch settings
Rotary switch settings (see example below) are used to determine the following items in your system, so you
should plan carefully before setting the switches.
•
If you use a
Default IP address
, the final octet is the number created by the three rotary switch settings (must
be a unique number from 1 to 253). See
To set the IP address
(page 19).
•
If you autogenerate the following:
Device Instance
, the number is automatically set to a number equal to the ((IP network number x 100) +
rotary switch settings).
BACnet Network Number
for Port S1, the number is automatically set to a number equal to the ((IP network
rotary switch settings) x 10).
Autogenerating is set up through the
controller setup pages
(page 47).
•
The rotary switch settings determine the router number in the i-Vu® interface.
EXAMPLE
The switches below are set to 125.
CAUTION
Do not leave the rotary switches set at 0 (the factory default). The TV-MPCXP cannot be discovered
if the rotary switches are left at 0.