Adjusting the TV-MPCXP driver properties
TruVu™ MPC Processor
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
43
I/O Bus and Xnet Expanders
The
I/O Bus and Xnet Expanders
page provides the configuration and status information described in the table
below.
I/O Bus Configuration
Maximum I/O Bus Expanders
The controller can have no more than 9 TruVu
TM
MPC I/O expanders.
Communication Timeout
If the TruVu
TM
MPC I/O expander does not receive communication from the
controller for this amount of time, the expander will reset itself. The range is 15
–
300 seconds.
I/O Bus Status
The table shows information for all TruVu
TM
MPC I/O expanders that are
communicating with the TV-MPCXP.
Status
Possible statuses
Description
Operational
TruVu
TM
MPC I/O expander is operating correctly.
Error: Comm Fail
The controller and TruVu
TM
MPC I/O expander are not
communicating.
Error: Unsupported
Type
The TruVu
TM
MPC I/O expander type is not compatible
with the controller firmware version.
Disabled
Status briefly shown before
Error: Comm Fail
appears.
Download Required
The version of firmware in the TruVu
TM
MPC I/O
expander is different than expander firmware in the TV-
MPCXP.
Downloading
The TruVu
TM
MPC I/O expander's firmware is being
upgraded.
Boot Running
Status briefly shown before
Download Required
appears.
Error: Calibration
TruVu
TM
MPC I/O expander was not calibrated in the
factory. Please return.
Error: 15V Power
Supply
TruVu
TM
MPC I/O expander has detected an issue with
its 15V power supply.
Error: 5V Power Supply
TruVu
TM
MPC I/O expander has detected an issue with
its 5V power supply.
Input
and
Output Numbers
The number of inputs, HAOs, and outputs on the expander.
FW Version
The version of firmware that is in the expander.
Hardware Type
The number in this column should appear in the list of
Expander Types Supported
in the
I/O Bus Firmware Inventory
section.
Network Termination
Shows if the expander's I/O Bus
End of Net?
switch is set to
Yes
(On) or
No
(Off).
Model Type