Troubleshooting
TruVu™ MPC Processor
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
55
Sys (System Status) Tricolor LED
Color
Pattern
Condition
Message in Module
Status
Possible Solution
Green
3 blink
BACnet Device ID is not set
Download required
Download the controller
Green
Fast
blink
Installation of recently downloaded
driver is occurring
N/A
No action required
Blue
On
Controller is starting up
N/A
No action required
Blue
Slow
blink
Linux (operating system) is starting up
N/A
No action required
Blue
Fast
blink
Linux is running but it could not start
the firmware application
N/A
Download driver
To get a Module Status report
A Module Status report provides information about the controller and verifies proper network communication with
the controller. You can get this report:
•
In the i-Vu® application
—
Right-click the controller on the navigation tree, then select
Module Status
.
•
In the Field Assistant application
—
Right-click the controller in the navigation tree and select
Module Status
.
•
On the controller setup
ModStat
tab
—
See
To set up the controller through the Service Port
(page 47).
See
Module Status field descriptions
(page 59) in the Appendix.
To get a Device Log
If Carrier Control Systems Support instructs you to get the controller's Device Log containing diagnostic
information for troubleshooting:
1
Select the TV-MPCXP in the i-Vu® navigation tree.
2
On the
Properties
page, click
Device Log
.
NOTE
You can click
Device Log Archive
to download a file containing multiple Device Logs to your computer. This
also contains any network packet captures that have been run from the
Network Diagnostics - Packet Captures
(page 41) driver page.