What
is the TruVu™ MPC Processor?
TruVu™ MPC Processor
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
4
Protection
The TV-MPCXP has two fast acting, 5mm x 20mm glass fuses:
•
A 2A fuse for the TV-
MPCXP’s power
•
A 4A fuse for the I/O bus edge connector
The power and network ports comply with the EMC requirements EN50491-5-2.
CAUTION
To protect against large electrical surges on serial EIA-485
networks, place a PROT485 at each place wire enters or exits the building.
LED status indicators
•
Tricolor
Net
LED to show network status
•
Tricolor
Sys
LED to show system status
•
A
Tx
(Transmit) and
Rx
(Receive) LED for the following ports:
○
Gig-E
○
I/O Bus
○
Port S1
○
Port S2
○
Xnet
○
Rnet
See
LEDs
(page 53).
Environmental operating
range
-40 to 158°F (-40 to 70°C), 10-95% relative humidity, non-condensing
NOTES
•
The TV-MPCXP is suitable for installation inside or outside the building
envelope.
•
Install in a UL Listed enclosure only.
•
Do not change the position of the power or
End of Net
switch at temperatures
below -22°F (-30C) to ensure proper operation and electrical connectivity.
Physical
Fire-retardant plastic ABS, UL94-5VA
Terminal blocks and
connectors
Screw-type terminal blocks.
0.2 in (5.08 mm) pitch connectors
Mounting
35mm DIN rail mounting or screw mounting
Overall dimensions
A:
B:
Depth:
7.1 in. (18.03 cm)
6.95 in. (17.65 cm)
2.09 in. (5.31 cm)
Screw mounting dimensions C:
D:
6.45 in (16.38 cm)
4.1 in. (10.4 cm)
Weight
1 lb. (0.45 kg)
BACnet support
Conforms to the BACnet Building Controller (B-BC) Standard Device Profile as
defined in ANSI/ASHRAE Standard 135-2012 (BACnet) Annex L, Protocol Revision
14