What
is the TruVu™ MPC Processor?
TruVu™ MPC Processor
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
2
The TV-MPCXP has 4 physical ports for BACnet or Modbus communication:
Port
Port type
For routing this type
of communication...
At...
Gig-E
10/100/1000 Mbps Ethernet
BACnet/IP,
BACnet/Ethernet, and/or
Modbus TCP/IP
10, 100, or 1000 Mbps
(1 Gbps)
S1
High-speed EIA-485 port
BACnet/ARCNET
or
BACnet/MSTP
or
Modbus Serial
156 kbps
9.6 to 115.2 kbps
9.6 to 115.2 kbps
S2
Electrically isolated EIA-485 port
BACnet/MSTP
or
Modbus Serial
9.6 to 115.2 Kbps
9.6 to 115.2 kbps
Service
Port
10/100 Mbps Ethernet
HTTP/IP
BACnet/IP Service Port
10 or 100 Mbps
The TV-MPCXP also has the following ports:
•
I/O Bus port for wired TruVu
TM
MPC I/O expanders
•
I/O bus edge connector for directly-connected TruVu
TM
MPC I/O expanders
•
Xnet port for MPC Open XPIO expanders
•
Rnet port for ZS sensors, Wireless Adapter for wireless sensors, and an Equipment Touch
•
USB port for recovery
•
Ethernet Service Port for connecting l
ocally to controller setup pages and the TruVu™ ET Display
Specifications
Driver
drv_fwex_< version >.driverx
Maximum number of control programs*
999
Maximum number of BACnet objects*
12000
Third-party BACnet integration points
1500
Third-party Modbus integration points
200
* Depends on available memory.